Genset solves hospital’s standby power needs

A generator set installation at a Cape Town private hospital provides a plug-and-play solution with high reliability and minimal downtime.

“In a design that suited the hospital’s severe space constraints, Zest WEG built the generator, transformer and remote radiator into special ISO shipping containers in a double-stack configuration,” explained Johannes Nel, operations manager – production at Zest WEG. “The contract also included the refurbishment of the client’s existing 1 000 kVA 400V MTU open-type generator which was included in the solution.”

The new genset expands the hospital’s standby generating capacity to 1 MVA continuous rating, allowing 100% of the institution’s functions to continue as normal during periods of load-shedding. Nel also highlights that reliable supply was key to the hospital’s safe and efficient operation, whether from mains or back-up supply.

To reduce the project lead time as much as possible, the delivery of certain imported components was arranged well in advance. The containerised solution was constructed and extensively tested at the Zest WEG genset manufacturing facility in Epping, saving time during installation.

“It was critical that any downtime be kept to an absolute minimum, as hospitals need to run continuously,” Nel says. “With our expertise, product range and experience in the health sector, our design, installation and commissioning strategy was able to align closely with this priority.”

A dry-type step-up transformer allows the generator to connect to the 11 kV council electricity supply council supply, which will reduce hospital downtime during commissioning. The resin-sealed transformer also provides a long-lasting solution with low maintenance and a high safety factor due to the absence of oil as a coolant.

Nel explains that another vital concern was the hospital’s proximity to a residential area, demanding that the noise level of the generator be kept within strict limits. This requirement was successfully achieved during testing, with the noise level kept within 65 decibels at a distance of seven metres.

In addition to conducting a complete engine rewiring, Zest WEG also upgraded the generator controller, giving the customer improved ability to monitor the generator’s operation during load-shedding. The modern controls help protect the generator and optimise the lifespan of critical equipment.

To enquire about Cape Business News' digital marketing options please contact sales@cbn.co.za

Related articles

City replaces over 20km of water and sewer pipes in February

THE City of Cape Town’s Water and Sanitation Directorate successfully replaced 22 255m of water and sewer pipes in February 2025, as part of...

B20 South Africa 2025 Moves from Cape Town to Joburg

By Larry Claasen THE initial plan for Cape Town to host the B20 South Africa 2025, the business-oriented summit of the G20 South Africa 2025,...

MUST READ

City delivering real change

Behind every budget line, every policy, and every project there are real people, real challenges, and a shared future we are shaping. In a...

RECOMMENDED

Privacy Overview

This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.

Strictly Necessary Cookies

Strictly Necessary Cookie should be enabled at all times so that we can save your preferences for cookie settings.

If you disable this cookie, we will not be able to save your preferences. This means that every time you visit this website you will need to enable or disable cookies again.